top of page

dpt-ctrl

pid controllers

WITH DIFFERENTIAL PRESSURE OR AIRFLOW TRANSMITTER

wp4628172-hvac-wallpapers_edited.jpg
DPT_Ctrl.png

DPT-CTRL

DPT-Ctrl is a multifunctional PID controller with differential pressure or air flow transmitter. It enables controlling constant pressure or flow of fans, VAV systems or dampers. When controlling flow, it is possible to select a fan manufacturer or a common measuring probe that has a K-value.

 

USAGE & APPLICATIONS

DPT-Ctrl can be used to control air flow or constant pressure in applications where it is important to keep a constant vacuum or a steady air flow, such as vacuuming units in renovation sites that keep a constant negative pressure so that impurities do not spread to other spaces.

Technical Specifications

Accuracy (from applied pressure):


Accuracy (from applied pressure):

Measuring units:

Control signal:

Output signal for pressure or airflow (selectable via menu):

PID-parameters:


Zero point calibration:

Supply voltage:

 

Power consumption:

Operating temperature: 

Protection standard:

Pressure < 125 Pa = 1 % + ±2 Pa (model 2500)

Pressure > 125 Pa = 1 % + ±1 Pa

Pressure < 125 Pa = 1.5 % + ±2 Pa (model 7000)

Pressure > 125 Pa = 1.5 % + ±1 Pa

Pressure: Pa, kPa, mbar, inchWC, mmWC, psi Flow: m3/s, m3/h, cfm, l/s, m/s, ft/min

0...10 VDC

0…10 VDC

4…20 mA

Adjustable via menu

Automatic with autozero element (-AZ) or by pushbutton

24 VDC ±10 % / 24 VAC ±10 %

< 1.0 W

-20…+50 °C with autozero (-AZ) calibration -5...+50 °C -40…+50 °C (-40C model)

IP54